Skip to main content

+675 307-2025atlascopcopng@higharctic.com

Power Calculator

Estimate the generator size for your site, or convert between kVA, kW and amps.

Our in-house calculators can assist with a range of analysis on:

  • Fuel savings
  • CO₂ emissions reductions
  • Total cost savings: ownership compared with rental
  • Return on capital
Talk to our team
Supply

Usually 0.8. From 0.5 to 1.0.

Add up the running power of everything the generator will supply. Up to 5,000 kW.

Recommended Generator Size

Enter your total load to see the recommended size.

How to ConvertkVA to kW

kVA measures apparent power. kW measures the real power your equipment uses. The power factor links the two, and most generators are rated at a power factor of 0.8.

kW = kVA × power factor

Example: 100 kVA × 0.8 = 80 kW

Sizing for Motors and Transformers

Motors and transformers draw a surge of power when they start. It's typically around six times their normal running current, and close to double that for modern high-efficiency motors.

Sizing a generator on that surge alone often means buying a bigger generator than the job needs. Other factors matter too, such as harmonics from variable speed drives and whether motors start one after another.

Many Atlas Copco generators can be fitted with options that handle the starting surge, so a smaller generator can do the job:

  • Permanent magnet or auxiliary winding excitation: gives the generator up to three times its rated current for at least ten seconds.
  • Digital automatic voltage regulator (D-AVR): manages starting surges smoothly, which can allow a smaller generator.
  • Close Before Excitation: brings the voltage up gradually as the engine starts. This is useful for powering step-up transformers on medium-voltage sites.

The result is a right-sized generator with lower running costs and a longer working life. Talk to our team about your motor and transformer loads.

Contact us